Function

High-temperature desuperheaters are used for temperature control in boiler superheaters (HP) and reheaters.

In addition, desuperheaters are utilized to regulate steam temperature, provide process steam, and protect downstream temperature-sensitive components.

Design

  • Forged body with flanged connections or butt-weld ends.
  • Actuator type freely selectable – hydraulic, pneumatic, or electric.

Benefits

The controllable desuperheaters form an integrated unit consisting of a cooling water control valve and a nozzle head.

  • Fine cooling water atomization even in the partial load range.
  • Precise setting of the specified temperature through accurate dosing of the injection volume.
  • High turndown ratio of 1:25 achieved by sealing inactive nozzles with piston rings.
  • Pre-throttling in 1 to max. 3 control stages, ensuring low-wear performance even with large pressure drops.
  • Drip-tight in the closed position
  • Equipped as standard with an upstream strainer.
  • All internal parts are replaceable without the need for mechanical machining.
  • Nozzle position / flange arrangement can be customized individually.